Study guide · General Building (B) · Core Trades
Electrical: The Rules the Exam Asks For
About 30 minutes · 7 sections
What this guide covers
Electrical is the second-largest slice of Core Trades on the exam. Most questions test one definition, one number, or one location rule from the California Electrical Code. Where a feeder ends. How many circuits feed the countertops. Which rooms need GFCI and which need AFCI. Where neutral and ground meet. How deep the working space is. This guide carries those facts at the grain the exam tests them.
Key terms
- Feeder
- The conductors between the service equipment (or other supply source) and the final branch-circuit overcurrent device.
- Branch circuit
- The conductors between the final overcurrent device and the outlets.
- Equipment grounding conductor (EGC)
- The conductive path that connects normally non-current-carrying metal parts to the system grounded conductor or the grounding electrode conductor.
- Outlet
- A point on the wiring system where current is taken to supply utilization equipment. A receptacle outlet is one with a receptacle installed.
The rules the exam tests
5 rules · 2 minDefinitions
A feeder starts at the main panel or at a .
A feeder is all the circuit conductors between the service equipment, the source of a separately derived system, or another power supply source and the final branch-circuit overcurrent device. On a house, that's the main panel to a subpanel.
On the job
Main panel to subpanel is the everyday feeder. The definition also reaches conductors from a separately derived system or another power supply source, which only the feeder definition carries.
Exact wording
A feeder is all the circuit conductors between the service equipment, the source of a separately derived system, or another power supply source and the final branch-circuit overcurrent device. On a house, that is the run from the main panel to a subpanel.
Electrical Code § art100
The branch circuit starts at the final overcurrent device and runs to the outlets.
A has two or more conductors with voltage between them and one neutral with equal voltage to each, connected to the system neutral. Either way, the device at the start protects that circuit, and the run ends at the outlet or outlets.
On the job
Feeder and branch circuit meet at the final overcurrent device: everything after it is branch circuit. The multiwire definition sets up the simultaneous-disconnect rule.
Exact wording
A branch circuit is the circuit conductors between the final overcurrent device protecting the circuit and the outlet or outlets. A multiwire branch circuit has two or more ungrounded conductors with voltage between them and one neutral with equal voltage to each, connected to the system neutral.
Electrical Code § art100
The connects the system or equipment to a grounding electrode.
A grounding electrode is a conducting object that makes a direct connection to earth. The GEC connects the system or the equipment either to a grounding electrode or to a point on the grounding electrode system.
On the job
Three grounding conductors sound alike. The GEC is the one that goes to earth; the equipment grounding conductor bonds metal parts; the grounded conductor is the intentionally grounded circuit conductor, which in a dwelling is the neutral.
Exact wording
A grounding electrode is a conducting object that makes a direct connection to earth. The grounding electrode conductor (GEC) connects the system grounded conductor or the equipment to a grounding electrode, or to a point on the grounding electrode system.
Electrical Code § art100
The makes the neutral-to-ground connection at the service.
The main bonding jumper's two ends are the grounded circuit conductor — in a dwelling, the neutral — and the equipment grounding conductor, the , or both. A separately derived system, a power supply output other than a service with no direct connection to another source except through grounding and bonding, makes the same connection through its own .
On the job
The exam tests where neutral and ground are tied together: at the service by the main bonding jumper, and again at each separately derived system by the system bonding jumper. Downstream of those points, on new work, they stay apart.
Exact wording
The main bonding jumper is the connection at the service between the grounded circuit conductor (in a dwelling, the neutral) and the equipment grounding conductor, the supply-side bonding jumper, or both. A separately derived system, a power supply output other than a service with no direct connection to another source except through grounding and bonding, gets the same connection through its own system bonding jumper.
Electrical Code § art100
A service lateral is the underground conductors ending at the .
A service drop is the overhead conductors between the utility and the service point. The service lateral's underground conductors begin at the utility's electric supply system. The service point is where the utility's facilities connect to the premises wiring.
On the job
Lateral means underground; drop means overhead. Both end at the service point, which is the boundary between the utility and the customer.
Exact wording
A service lateral is the underground conductors between the utility's electric supply system and the service point. A service drop is the overhead conductors between the utility and the service point. The service point is where the utility's facilities connect to the premises wiring.
Electrical Code § art100
Take away
6 rules · 5 minBranch circuits and receptacles
Run at least two 20-ampere small-appliance branch circuits in every dwelling unit. More are allowed.
Small-appliance circuits serve the receptacle outlets required by the kitchen receptacle rule. A dwelling unit also needs at least one 20-ampere laundry circuit with no other outlets, and one or more 120-volt, 20-ampere bathroom circuits supplying the required bathroom receptacle outlets and any countertop or similar work-surface receptacle outlets, with no other outlets — except that a circuit serving a single bathroom may also supply other equipment in that bathroom. A dwelling unit needs at least one 120-volt, 20-ampere garage circuit for the receptacle outlets of an attached garage or a detached garage with electric power, with no other outlets — except that this circuit may also supply outdoor receptacle outlets and, where it serves a garage with a single vehicle bay, other equipment in that garage. Garage receptacle outlets beyond the required ones may go on additional branch circuits rated 15 amperes or greater.
On the job
Two is the minimum tested number of 20-amp small-appliance circuits; more are permitted. The laundry, bathroom, and garage circuits are the neighbors. The qualifiers are the single-bathroom allowance and the garage circuit's outdoor-receptacle and single-vehicle-bay allowances.
Exact wording
A dwelling unit needs two or more 20-ampere small-appliance branch circuits for the receptacle outlets the kitchen-receptacle section requires. It also needs at least one 20-ampere laundry circuit with no other outlets, and one or more 120-volt, 20-ampere bathroom circuits supplying the required bathroom receptacle outlets and any countertop or similar work-surface receptacle outlets, with no other outlets, except that a circuit serving a single bathroom may also supply other equipment in that bathroom. It also needs at least one 120-volt, 20-ampere garage circuit for the receptacle outlets of an attached garage or a powered detached garage, with no other outlets, except that it may supply outdoor receptacle outlets and, where it serves a single-vehicle-bay garage, other equipment in that garage. Garage receptacle outlets beyond the required ones may be served by additional branch circuits rated 15 amperes or greater.
Electrical Code § 210.11
Feed your kitchen countertop receptacles from at least two 20-ampere small-appliance circuits.
Small-appliance branch circuits are the two or more 20-ampere circuits that 210.11(C)(1) requires. In a dwelling unit's kitchen, pantry, breakfast room, dining room, and similar areas, they serve all the 125-volt, 15- and 20-ampere wall, floor, and countertop receptacle outlets and the receptacle outlets for refrigeration equipment. No small-appliance circuit may serve more than one kitchen. Put no other outlets on those circuits, except a receptacle installed solely to supply an electric clock in those rooms and receptacles for the supplemental equipment and lighting on gas-fired ranges, ovens, or counter-mounted cooking units. In addition to the required receptacles, you may supply a receptacle serving a specific appliance from an rated 15 amperes or greater, and you may feed a switched receptacle permitted by 210.70(A)(1) Exception No. 1 from a general-purpose 15- or 20-ampere circuit.
On the job
The exam asks how many circuits feed the countertop receptacles: at least two, and they may not cross into a second kitchen. The refrigerator rides on them unless it gets its own circuit.
Exact wording
In the kitchen, pantry, breakfast room, dining room, and similar areas of a dwelling unit, for the 125-volt, 15- and 20-ampere receptacle outlets this section governs, the two or more 20-ampere small-appliance circuits that 210.11(C)(1) requires serve all the wall, floor, and countertop receptacle outlets and the receptacle outlets for refrigeration equipment; in addition to those required receptacles, a receptacle outlet serving a specific appliance may be supplied from an individual branch circuit rated 15 amperes or greater. Those small-appliance circuits have no other outlets, except a receptacle installed solely to supply an electric clock in those rooms and receptacles for the supplemental equipment and lighting on gas-fired ranges, ovens, or counter-mounted cooking units. Receptacles serving kitchen countertops must be supplied by at least two small-appliance circuits, and no small-appliance circuit may serve more than one kitchen. In addition to the required receptacles, a switched receptacle permitted by the lighting-outlet rule, 210.70(A)(1) Exception No. 1, may be fed from a general-purpose 15- or 20-ampere circuit.
Electrical Code § 210.52
Fixed panels count as wall space for receptacle spacing. Sliding panels do not.
Wall space means any wall 2 feet or wider, measured around corners and unbroken along the floor line by doorways, fireplaces, stationary appliances, or fixed cabinets without countertops. It also includes the space occupied by fixed panels in walls — the stationary leaf of a sliding glass door — but not sliding panels, and the space at fixed room dividers such as bar-type counters or railings. Place receptacles so no point along the floor line of any wall space is more than 6 feet from a receptacle outlet. Do not count a receptacle that is part of a luminaire or appliance, controlled by a listed wall-mounted control device, inside a cabinet or cupboard, or more than 5-1/2 feet above the floor. A floor receptacle counts only if it is within 18 inches of the wall. A factory-installed or manufacturer-supplied receptacle on a permanently installed electric baseboard heater may serve as the required outlet for that wall space, provided it is not connected to the heater circuit.
On the job
The 6-foot rule is the basic number: no point on a wall space more than 6 feet from a receptacle, so no gap wider than 12 feet. The tested trap is the sliding glass door: its fixed panel counts as wall space and needs coverage; the sliding panel does not.
Exact wording
Receptacles are placed so that no point along the floor line of any wall space is more than 6 feet from a receptacle outlet. For receptacle spacing, wall space includes any wall 2 feet or wider, measured around corners and unbroken along the floor line by doorways, fireplaces, stationary appliances, or fixed cabinets without countertops. It also includes the space occupied by fixed panels in walls, but not sliding panels, and the space at fixed room dividers such as bar-type counters or railings. A receptacle that is part of a luminaire or appliance, controlled by a listed wall-mounted control device, inside a cabinet or cupboard, or more than 5-1/2 feet above the floor does not count toward the required outlets. A floor receptacle counts only if it is within 18 inches of the wall. A factory-installed or manufacturer-supplied receptacle on a permanently installed electric baseboard heater may serve as the required outlet for that wall space, provided it is not connected to the heater circuit.
Electrical Code § 210.52
Give every one disconnect that opens all its hot legs together.
The disconnecting means sits at the point where the circuit originates and opens every conductor of that circuit simultaneously. All conductors of a multiwire branch circuit originate from the same equipment containing its overcurrent devices, except as the wiring methods article permits.
On the job
A shared neutral with two hot legs can still be live when one breaker is off. The code answers with a common disconnect: a two-pole breaker or handle tie at the panel.
Exact wording
Every multiwire branch circuit must have a means that simultaneously disconnects all its ungrounded conductors at the point where the circuit originates. All conductors of a multiwire circuit originate from the same equipment containing its overcurrent devices, except as the wiring-methods article permits.
Electrical Code § 210.4
You may skip the island receptacle, but you must leave provisions for adding one later.
In dwelling kitchens, pantries, breakfast rooms, dining rooms, and similar areas, every countertop or work surface 12 inches or wider gets 125-volt, 15- or 20-ampere receptacle outlets, and those do not count toward the wall-space outlets. Along a countertop wall, no point on the wall line may be more than 24 inches horizontally from a receptacle outlet — except that none is required directly behind a range, counter-mounted cooking unit, or sink in the configuration the code's figure shows, and except that where a required outlet cannot go in the wall areas that figure shows, it goes as close as practicable to the countertop it serves, without reducing the count. An island or peninsula need not have a receptacle, but if you install none, provisions for adding one later are required. Put countertop receptacles on or above the surface but not more than 20 inches above it, or use listed countertop or work-surface receptacle assemblies; and a receptacle does not count as a required outlet if an appliance fastened in place, an appliance garage, a sink or rangetop in the Exception No. 1 configuration, or an appliance occupying an assigned space makes it not . Each 12 inches of multioutlet assembly containing two or more receptacles, installed in individual or continuous lengths, counts as one outlet.
On the job
The exam tests the 24-inch countertop spacing (against the 6-foot wall-space rule), the 20-inch height limit, and the newer island rule: a receptacle is optional on an island, but provisions for one are not.
Exact wording
In kitchens, pantries, breakfast rooms, dining rooms, and similar areas of dwelling units, countertop and work surfaces 12 inches or wider get 125-volt, 15- or 20-ampere receptacle outlets that do not count toward the general wall-space outlets. Along a countertop wall, no point along the wall line may be more than 24 inches horizontally from a receptacle outlet, except that none is required directly behind a range, counter-mounted cooking unit, or sink in the configuration the code's figure shows, and where a required outlet cannot go in the wall areas the figure shows, it goes as close as practicable to the countertop it serves without reducing the count. An island or peninsula need not have a receptacle, but if none is installed, provisions for adding one later are required. Countertop receptacles are located on or above the surface but not more than 20 inches above it, or in listed countertop or work-surface receptacle assemblies; receptacles made not readily accessible by appliances fastened in place, appliance garages, sinks or rangetops in the behind-the-range-or-sink configuration of Exception No. 1, or appliances occupying assigned spaces do not count as required outlets. Each 12 inches of multioutlet assembly containing two or more receptacles, installed in individual or continuous lengths, counts as one outlet.
Electrical Code § 210.52
Divide watts by volts to get amperes on a single-phase circuit.
Given two of the three — watts, volts, amperes — you find the third. A 1,500-watt heater on a 120-volt circuit draws 1,500 ÷ 120 = 12.5 amperes, assuming a resistive load with a power factor of 1.
On the job
The exam gives watts and volts and asks for amps, or gives amps and volts and asks for watts. Watts = volts × amperes, turned whichever way the question needs.
Exact wording
On a single-phase circuit, current in amperes equals power in watts divided by voltage in volts. Two of the three quantities are given; the third is found from them. Example: a 1,500-watt heater on a 120-volt circuit draws 1,500 ÷ 120 = 12.5 amperes, assuming a resistive load with a power factor of 1.
Standard trade practice
Take away
8 rules · 6 minGFCI and AFCI
In dwellings, GFCI-protect the 125- to 250-volt receptacles in the listed locations.
GFCI is ground-fault circuit interrupter protection. In dwelling units, GFCI-protect all 125- through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground in these locations: bathrooms; garages and accessory buildings with a floor at or below grade level used for storage or work; outdoors; crawl spaces at or below grade; basements; kitchens; areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking; within 6 feet of the top inside edge of a sink bowl; boathouses; within 6 feet of the outside edge of a bathtub or shower stall; laundry areas; and indoor damp and wet locations. Measure those 6 feet along the shortest path a cord would follow without passing through a wall, floor, ceiling, or fixed barrier. Install the GFCI where it is .
On the job
Bathrooms and kitchens are the tested locations, and the receptacle range covers 125 through 250 volts. Readily accessible is the installation rule that follows.
Exact wording
In dwelling units, all 125- through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground need GFCI protection in these locations: bathrooms; garages and accessory buildings with a floor at or below grade level used for storage or work; outdoors; crawl spaces at or below grade; basements; kitchens; areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking; within 6 feet of the top inside edge of a sink bowl; boathouses; within 6 feet of the outside edge of a bathtub or shower stall; laundry areas; and indoor damp and wet locations. Distances are measured along the shortest path a cord would follow without passing through a wall, floor, ceiling, or fixed barrier. The GFCI must be installed in a readily accessible location.
Electrical Code § 210.8
Two exceptions excuse dwelling GFCI protection, but only where the receptacle is not readily accessible.
The first exception covers a receptacle on a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating: that receptacle follows those articles' own ground-fault rules instead. The second covers a factory-installed receptacle mounted inside a bathroom exhaust fan assembly, exempt unless its instructions or listing require GFCI. Both receptacles must be not readily accessible. These are only two of the code's four exceptions.
On the job
The exceptions are the qualifiers a question hides: a sealed-in fan receptacle, a dedicated deicing circuit. The list here is not the whole list; the code has four.
Exact wording
Two of the four exceptions to the dwelling GFCI locations: a receptacle that is not readily accessible and is on a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating may follow those articles' own ground-fault rules instead, and a factory-installed receptacle mounted inside a bathroom exhaust fan assembly and not readily accessible is exempt unless its instructions or listing require GFCI.
Electrical Code § 210.8
Protect every outdoor outlet in a dwelling with GFCI. Your hardwired condenser counts as an outlet.
A condenser wired in with no plug still sits at an outlet, so the rule reaches it. In dwellings, the requirement covers single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less, including outlets in garages with floors at or below grade, accessory buildings, and boathouses. If you replace the equipment an outdoor outlet supplies, that outlet needs GFCI protection. Excluded: not-readily-accessible receptacles on branch circuits dedicated to snow-melting, deicing, or pipeline and vessel heating. Lighting outlets are excepted, but crawl-space lighting outlets at 120 volts or less still need GFCI under 210.8(C). Listed HVAC equipment is excepted only until September 1, 2026.
On the job
Outlet is broader than receptacle: a hardwired condenser is still supplied from an outlet even though no receptacle is involved. The exam tests that the rule reaches it, and the HVAC exception's expiration date.
Exact wording
For dwellings, all outdoor outlets, not only receptacles, on single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less need GFCI protection, including outlets in garages with floors at or below grade, accessory buildings, and boathouses. If the equipment an outdoor outlet supplies is replaced, the outlet gets GFCI protection. The same not-readily-accessible receptacles on branch circuits dedicated to snow-melting, deicing, or pipeline and vessel heating are excluded, lighting outlets are excepted except that crawl-space lighting outlets at 120 volts or less still need GFCI under 210.8(C), and listed HVAC equipment was excepted only until September 1, 2026, the date on which the code says that exception expires.
Electrical Code § 210.8
Put GFCI protection on the range, dryer, and dishwasher circuits wherever you install them.
Ground-fault circuit-interrupter protection goes on the branch circuit or outlet supplying the appliance, so the protection follows the appliance, not the room. It covers appliances rated 150 volts or less to ground and 60 amperes or less, single- or three-phase: dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, microwave ovens, sump pumps, drinking water coolers and bottle-fill stations, vending machines, automotive vacuum machines, tire inflation machines, and high-pressure spray washing machines.
On the job
The exam tests that appliance GFCI follows the appliance, not the room: a dryer or range circuit needs GFCI protection because it is on the 210.8(D) list, not because of where it sits. The voltage and ampere limits are the qualifiers a question hides.
Exact wording
GFCI protection is required for the branch circuit or outlet supplying certain appliances rated 150 volts or less to ground and 60 amperes or less, single- or three-phase, wherever they are installed: dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, microwave ovens, sump pumps, drinking water coolers and bottle-fill stations, vending machines, automotive vacuum machines, tire inflation machines, and high-pressure spray washing machines.
Electrical Code § 210.8
You need AFCI on nearly every living area circuit in a dwelling unit.
AFCI stands for arc-fault circuit interrupter. In dwelling units, every 120-volt, single-phase, 10-, 15-, and 20-ampere branch circuit supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, and similar areas needs AFCI protection by one of the listed means. A listed combination-type AFCI protecting the whole branch circuit is the first of those means. Exception: no AFCI is needed for an supplying a fire alarm system installed per the fire-alarm article, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or AC cable, with metal boxes, conduit bodies, and enclosures.
On the job
Bedrooms are the tested location, but the list now covers nearly every living area of a dwelling unit.
Exact wording
In dwelling units, all 120-volt, single-phase, 10-, 15-, and 20-ampere branch circuits supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, and similar areas need AFCI protection by one of the listed means. A listed combination-type AFCI protecting the whole branch circuit is the first of those means. Exception: an individual branch circuit supplying a fire alarm system installed per the fire-alarm article, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or AC cable, with metal boxes, conduit bodies, and enclosures, needs no AFCI.
Electrical Code § 210.12
You must add arc-fault protection when you modify, replace, or extend an existing circuit.
An AFCI is an arc-fault circuit interrupter. The rule covers any 120-volt, single-phase, 10-, 15-, or 20-ampere branch circuit in a location where AFCI protection is required: the 210.12(B) dwelling-unit rooms (kitchens, bedrooms, living areas, hallways, closets, laundry areas, and similar); dormitory-unit bedrooms, living rooms, hallways, closets, bathrooms, and similar rooms, but not dormitory kitchens or laundry areas; hotel and motel guest rooms and suites; areas used exclusively as patient sleeping rooms in nursing homes and limited-care facilities; and areas designed for use exclusively as sleeping quarters in fire, police, ambulance, rescue, and ranger stations. Protect the circuit either by one of the listed means, or by a listed outlet branch-circuit-type AFCI at the first receptacle outlet of the existing branch circuit. The AFCI is listed and installed in a readily accessible location.
On the job
The remodel trap: extending an old bedroom circuit to add receptacles is not grandfathered. The exam tests that the modification triggers AFCI, and that the first-outlet AFCI device is the allowed retrofit.
Exact wording
Where the wiring of a 120-volt, single-phase, 10-, 15-, or 20-ampere branch circuit in any location where AFCI is required — the 210.12(B) dwelling-unit rooms (kitchens, bedrooms, living areas, hallways, closets, laundry areas, and similar), dormitory-unit bedrooms, living rooms, hallways, closets, bathrooms, and similar rooms (not dormitory kitchens or laundry areas), hotel and motel guest rooms and suites, areas used exclusively as patient sleeping rooms in nursing homes and limited-care facilities, and areas designed for use exclusively as sleeping quarters in fire, police, ambulance, rescue, and ranger stations — is modified, replaced, or extended, the circuit must be AFCI-protected: either by one of the listed means, or by a listed outlet branch-circuit-type AFCI at the first receptacle outlet of the existing branch circuit. The AFCI itself is listed and installed in a readily accessible location.
Electrical Code § 210.12
You may extend existing conductors up to 6 feet without adding AFCI protection.
AFCI means arc-fault circuit interrupter. The extension qualifies only if it adds no outlets or devices other than splicing devices. Length of conductor inside enclosures, cabinets, or junction boxes does not count toward the 6 feet.
On the job
Six feet and no added outlets or devices: the one carve-out from the modification rule. Splices are not devices; boxes and enclosures do not count toward the 6 feet.
Exact wording
The exception: an extension of the existing conductors of not more than 6 feet that adds no outlets or devices other than splicing devices needs no AFCI, and conductor length inside enclosures, cabinets, or junction boxes is not counted.
Electrical Code § 210.12
When you replace a receptacle, you meet today's GFCI and AFCI rules.
Where the code requires GFCI protection at the outlet, the replacement must provide that protection, and the GFCI must be listed. If the box is too small for a GFCI receptacle, install a receptacle of the existing type only if GFCI protection is provided upstream and the receptacle is marked "GFCI Protected" and, as applicable, "No Equipment Ground." Put replacement GFCI and AFCI receptacles in readily accessible locations. Replacing a receptacle in the areas 210.12(A), (B), or (C) name — dwelling units and dormitory units, not the other sleeping occupancies of 210.12(D) — needs a listed outlet branch-circuit AFCI receptacle, a receptacle protected by one, or protection by a listed combination-type AFCI breaker. The 210.12(E) short-extension exception does not excuse AFCI on a receptacle replacement.
On the job
The exam tests that replacement triggers today's rule: an old kitchen receptacle comes out, a GFCI-protected one goes in, and a bedroom receptacle comes out with AFCI protection going in. The small-box exception is the qualifier.
Exact wording
When a receptacle is replaced at an outlet that the code requires to be GFCI-protected, the replacement must provide GFCI protection, and the GFCI must be listed. Where the box is too small for a GFCI receptacle, a receptacle of the existing type may be installed if GFCI protection is provided upstream and the receptacle is marked "GFCI Protected" and "No Equipment Ground" as applicable. Replacement AFCI and GFCI receptacles go in readily accessible locations. Replacing a receptacle in the areas 210.12(A), (B), or (C) name — dwelling units and dormitory units, not the other sleeping occupancies of 210.12(D) — needs a listed outlet branch-circuit AFCI receptacle, a receptacle protected by one, or protection by a listed combination-type AFCI breaker. The 210.12(E) short-extension exception does not excuse AFCI on a receptacle replacement.
Electrical Code § 406.4
Take away
6 rules · 4 minGrounding and bonding
Wire the grounds so pulling a device out of the box leaves the ground path intact.
Where circuit conductors are spliced or terminated in a box, connect all the equipment grounding conductors in that box together. Run a pigtail from that splice to each receptacle, luminaire, or other device, rather than daisy-chaining the conductor through the device. In a nonmetallic box, arrange the equipment grounding conductors to connect to any device or fitting in the box that needs one.
On the job
The tested practice is the pigtail: the ground path must survive pulling a device. In a plastic box there is no box to bond, so the conductors themselves must reach every device.
Exact wording
Where circuit conductors are spliced or terminated in a box, all equipment grounding conductors in the box are connected together. The connections are arranged so that removing a receptacle, luminaire, or other device does not break the equipment grounding path, which means a pigtail to the device rather than a daisy-chain through it. In a nonmetallic box, the equipment grounding conductors are arranged to connect to any device or fitting in the box that needs one.
Electrical Code § 250.148
An equipment bonding jumper connects one portion of the equipment grounding conductor to another.
A bonding jumper generally is a conductor that ensures the required electrical conductivity between metal parts that are required to be electrically connected. An equipment bonding jumper is the connection between two or more portions of the equipment grounding conductor. Bonding means connected to establish electrical continuity and conductivity.
On the job
This is the name for the short conductor a candidate ties every day and rarely names. Where the grounding conductors in a box are joined and a pigtail runs from that joint to the device's grounding terminal, the pigtail is an equipment bonding jumper — a connection between two portions of the equipment grounding conductor, not a new grounding conductor and not the , which runs to the earth electrode instead.
Exact wording
An equipment bonding jumper is the connection between two or more portions of the equipment grounding conductor. A bonding jumper generally is a conductor that ensures the required electrical conductivity between metal parts that are required to be electrically connected, and bonding itself means connected to establish electrical continuity and conductivity.
Electrical Code § art100
On new work, never bond the neutral to ground at a second building.
A building or structure fed by a feeder or branch circuit needs its own grounding electrode system, unless a single branch circuit with an equipment grounding conductor supplies it. Run the EGC with the feeder to that building's disconnecting means and to its electrodes, and keep the neutral off both. Exception for older work: an installation made under a previous edition that permitted it may keep using the neutral as the ground-fault return path, but only where all three hold — no EGC run with the supply, no continuous metallic paths bonded between the buildings, and no ground-fault protection of equipment on the supply side.
On the job
The subpanel-in-a-detached-garage trap: on new work, neutral and ground stay separate there, and the building still gets its own electrode. Only a qualifying pre-existing installation may keep using the neutral as the fault-return path.
Exact wording
A building or structure supplied by a feeder or branch circuit needs its own grounding electrode system, unless a single branch circuit with an equipment grounding conductor supplies it. The feeder carries an equipment grounding conductor to the building's disconnecting means and to its electrodes. The grounded conductor (neutral) is not connected to the equipment grounding conductor or to the electrodes at that building. Exception for older work: where an installation made under a previous edition that permitted it has no equipment grounding conductor run with the supply, no continuous metallic paths bonded between the buildings, and no ground-fault protection of equipment on the supply side, the grounded conductor may keep serving as the ground-fault return path.
Electrical Code § 250.32
Add a second electrode unless you measured 25 ohms or less on the single rod.
You may skip the supplement only if the single electrode has a measured resistance to earth of 25 ohms or less. The supplemental electrode must be of another type, one the code recognizes in 250.52(A)(2) through (A)(8). Keep rod, pipe, and plate electrodes free of nonconductive coatings, and embed them below permanent moisture level where practicable. Where you install more than one rod, pipe, or plate electrode to meet this rule, space them at least 6 feet apart.
On the job
One rod is not enough unless someone measured 25 ohms or less. With no measurement, the answer is a second electrode, at least 6 feet from the first. The exam tests the number and the condition.
Exact wording
A single rod, pipe, or plate electrode must be supplemented by an additional electrode of another type the code recognizes in 250.52(A)(2) through (A)(8), unless the single electrode has a measured resistance to earth of 25 ohms or less. Rod, pipe, and plate electrodes are free of nonconductive coatings and, if practicable, embedded below permanent moisture level. Where multiple rod, pipe, or plate electrodes are installed to meet the rule, they are at least 6 feet apart.
Electrical Code § 250.53
Drive a ground rod at least 8 feet into the soil. Only rock changes that.
A rod or pipe electrode meets 8 feet two ways: at least 8 feet in contact with the soil, and driven to a depth of at least 8 feet. Where rock bottom stops the rod, drive it at an oblique angle no more than 45 degrees from vertical, or, where rock stops it at that angle too, bury it in a trench at least 30 inches deep. The upper end sits flush with or below ground level, unless both the above-ground end and the grounding electrode conductor attachment are protected against physical damage.
On the job
8 feet in the ground is the tested number; the 45-degree and 30-inch reliefs are what the exam offers when the rod hits rock. The flush-or-protected rule is the neighbor.
Exact wording
A rod or pipe electrode is installed with at least 8 feet in contact with the soil and driven to at least 8 feet. Where rock bottom is met, it is driven at an oblique angle no more than 45 degrees from vertical, or, where rock is met at that angle too, buried in a trench at least 30 inches deep. The upper end is flush with or below ground level unless the above-ground end and the grounding electrode conductor attachment are protected against physical damage.
Electrical Code § 250.53
If you use a metal underground water pipe as your electrode, add a second electrode.
The supplement must be another type of electrode recognized in 250.52(A)(2) through (A)(8). If you use a rod, pipe, or plate, it follows the rod, pipe, and plate electrode rules. Continuity may not depend on water meters or filters.
On the job
A water pipe can be replaced with plastic, so the code never lets it stand alone. The supplement is required outright; there is no 25-ohm exception here.
Exact wording
A metal underground water pipe used as a grounding electrode must be supplemented by an additional electrode of another type the code recognizes in 250.52(A)(2) through (A)(8). The grounding path may not depend on water meters or filters for continuity. If the supplement is a rod, pipe, or plate, it follows the rod rules.
Electrical Code § 250.53
Take away
9 rules · 7 minEquipment and workmanship
Keep clear working space in front of equipment likely to need work while energized.
The requirement applies at 1,000 volts nominal or less to ground. Take the depth from Table 110.26(A)(1) by voltage to ground and by Condition 1, 2, or 3, measured from the exposed live parts or the enclosure front, unless 110.26(A)(1)(a) through (c) or another code rule allows less. Width is the equipment's width or 30 inches, whichever is greater, and doors or hinged panels must open 90 degrees. Height runs from the floor to 6-1/2 feet or the equipment's height, whichever is greater; within that height, other equipment or support structures associated with the installation and sitting above or below, such as concrete pads, may extend up to 6 inches past the front. Of the height rule's three exceptions, the remodeler's case: in an existing dwelling unit, service equipment or an enclosed panelboard rated 200 amperes or less may sit where the working-space height is less than 6-1/2 feet.
On the job
Depth from the table, width at least 30 inches, height at least 6-1/2 feet: the working-space package. The exam gives a voltage and what faces the panel and asks for the depth; the width and height are the neighbors. The residential exception is the case a remodeler meets: a 200-ampere-or-less panel in an existing house may live under a low ceiling.
Exact wording
Equipment likely to need work while energized, at 1,000 volts nominal or less to ground, needs working space in front of it. The depth, measured from the exposed live parts or the enclosure front, comes from Table 110.26(A)(1) by voltage to ground and by what faces the equipment, except where the reliefs in 110.26(A)(1)(a) through (c) or another rule of the code allow less. The width is the equipment's width or 30 inches, whichever is greater, and must allow doors or hinged panels to open 90 degrees. The height runs from the floor to 6-1/2 feet or the equipment's height, whichever is greater; within that height, other equipment or support structures associated with the installation and located above or below the electrical equipment, such as concrete pads, may extend up to 6 inches beyond its front. Of the height rule's three exceptions, the one a remodeler meets: in an existing dwelling unit, service equipment or an enclosed panelboard rated 200 amperes or less may sit where the working-space height is less than 6-1/2 feet.
Electrical Code § 110.26
Keep 24 inches wide and 6-1/2 feet high clear with the equipment doors open.
Opened doors impede access when they leave an opening less than 24 inches wide and 6-1/2 feet high. Three reliefs follow: no working space is required behind or beside a dead-front assembly whose connections and fuses are all reachable from elsewhere, though 30 inches of horizontal space is required at the rear where the back must be opened to work on nonelectrical parts. Special permission can allow a smaller space where all exposed live parts are 30 volts rms, 42 volts peak, or 60 volts dc or less. In an existing building where you are replacing equipment, you may use Condition 2 clearance between dead-front switchboards, switchgear, enclosed panelboards, or motor control centers located across an aisle from each other, where written procedures prohibit opening both sides at once and only authorized qualified persons service them.
On the job
24 inches is the door-open access figure, not the working-space width; keep it apart from the 30-inch width. The three reliefs are the qualifiers the exam attaches to the table.
Exact wording
Open equipment doors may not impede access to or egress from the working space; access is impeded if opened doors leave less than 24 inches wide and 6-1/2 feet high. Three reliefs sit in the same subsection. No working space is required behind or beside a dead-front assembly whose connections and fuses are all reachable from elsewhere, though 30 inches of horizontal space is required at the rear where the back must be opened to work on nonelectrical parts. A smaller space may be allowed by special permission where all exposed live parts are 30 volts rms, 42 volts peak, or 60 volts dc or less. And in an existing building where equipment is being replaced, Condition 2 clearance may be used between dead-front switchboards, switchgear, enclosed panelboards, or motor control centers located across an aisle from each other, where written procedures prohibit opening both sides at once and only authorized qualified persons service them.
Electrical Code § 110.26
You may not store anything in the working space about electrical equipment.
Where normally enclosed live parts are exposed for inspection or servicing in a passageway or open space, the working space must be guarded. At least one entrance of sufficient area gives access to and egress from the working space. Where equipment containing overcurrent, switching, or control devices is rated 1,200 amperes or more and is over 6 feet wide, or where service disconnecting means grouped under 230.71(B) have a combined rating of 1,200 amperes or more and a combined width over 6 feet, an entrance at least 24 inches wide and 6-1/2 feet high is required at each end of the working space. One entrance is enough where the location gives a continuous and unobstructed way of egress, or where the working space is twice the required depth and the distance from the equipment to the nearest edge of the entrance is at least the Table 110.26(A)(1) minimum clear distance for that voltage and condition.
On the job
The exam tests that the working space stays clear (no storage) and that large gear gets an egress path at each end. The 1,200-ampere-and-6-foot trigger and the two single-entrance reliefs are the figures a question turns on.
Exact wording
Working space about electrical equipment may not be used for storage, and where normally enclosed live parts are exposed for inspection or servicing in a passageway or open space, the working space is guarded. At least one entrance of sufficient area gives access to and egress from the working space. Where equipment containing overcurrent, switching, or control devices is rated 1,200 amperes or more and is over 6 feet wide, or where service disconnecting means grouped under 230.71(B) have a combined rating of 1,200 amperes or more and a combined width over 6 feet, an entrance at least 24 inches wide and 6-1/2 feet high is required at each end of the working space. A single entrance is permitted where the location gives a continuous and unobstructed way of egress, or where the working space is twice the required depth and the distance from the equipment to the nearest edge of the entrance is at least the Table 110.26(A)(1) minimum clear distance for that voltage and condition.
Electrical Code § 110.26
Put listed panic hardware on any personnel door within 25 feet of 800-ampere equipment.
Equipment rated 800 amperes or more qualifies only when it contains overcurrent, switching, or control devices, and its width does not matter. Where such equipment is present and a personnel door intended for entrance to and egress from the working space sits less than 25 feet from the nearest edge of that space, the door opens 90 degrees in the direction of egress and has listed panic hardware or listed fire-exit hardware. Indoor working spaces about service equipment, switchboards, switchgear, enclosed panelboards, and motor control centers are illuminated. Automatic controls may not control all of that illumination, and no additional lighting outlet is required where an adjacent light source, or a switched receptacle permitted by 210.70(A)(1), Exception No. 1, already illuminates the space.
On the job
The 800-ampere door rule stands on its own — it does not require the 1,200-ampere, 6-foot-wide equipment of the egress rule — and the panel room must be lit. The 25-foot door distance is the figure a question turns on.
Exact wording
Where equipment rated 800 amperes or more contains overcurrent, switching, or control devices, whatever its width, and a personnel door intended for entrance to and egress from the working space is less than 25 feet from the nearest edge of the working space, that door opens at 90 degrees in the direction of egress and has listed panic hardware or listed fire-exit hardware. Indoor working spaces about service equipment, switchboards, switchgear, enclosed panelboards, and motor control centers are illuminated; automatic controls may not control all of that illumination, and no additional lighting outlet is required where an adjacent light source, or a switched receptacle permitted by 210.70(A)(1), Exception No. 1, already illuminates the space.
Electrical Code § 110.26
Give the panel 3 feet of clear depth at 0 to 150 volts to ground.
Above 150 volts the depth depends on what faces the live parts. At 151 to 600 volts to ground, Condition 1 takes 3 feet, Condition 2 takes 3 feet 6 inches, and Condition 3 takes 4 feet. At 0 to 150 volts to ground, Table 110.26(A)(1) requires 3 feet in every condition. Condition 1 is live parts on one side with nothing live or grounded opposite, or live parts on both sides effectively guarded by insulation. Condition 2 is live parts on one side and grounded parts opposite, with concrete, brick, and tile walls counting as grounded. Condition 3 is exposed live parts on both sides.
On the job
A 120/240-volt house panel is under 150 volts to ground: 3 feet, whatever faces it. The conditions matter above 150 volts, and a concrete wall across from the panel is Condition 2.
Exact wording
Table 110.26(A)(1): at 0 to 150 volts to ground, the minimum clear depth is 3 feet in every condition. At 151 to 600 volts it is 3 feet for Condition 1, 3 feet 6 inches for Condition 2, and 4 feet for Condition 3. Condition 1 is live parts on one side and nothing live or grounded on the other, or live parts on both sides effectively guarded by insulation. Condition 2 is live parts on one side and grounded parts on the other; concrete, brick, and tile walls count as grounded. Condition 3 is exposed live parts on both sides.
Electrical Code § table-110.26-a-1
Terminals have a specified torque value. Use a torque tool to reach it.
Tighten terminal connections to the torque value marked on the equipment or given in the manufacturer's instructions. Use an approved means to reach that value, such as a torque tool or a breakaway device with a visual indicator.
On the job
The tested fact is that torque is specified, not felt. A calibrated tool or an indicating device is how the installer proves it before energizing.
Exact wording
Terminal connections are tightened to the torque values marked on the equipment or given in the manufacturer's instructions, using an approved means to reach that value, such as a torque tool or a breakaway device with a visual indicator.
Electrical Code § 110.14
Keep overcurrent devices out of clothes closets and bathrooms. Never mount one over stairway steps.
Don't put overcurrent devices near easily ignitible material, such as in a clothes closet. Don't put them in bathrooms, showering facilities, or locker rooms with showers — only is allowed there. Never over the steps of a stairway.
On the job
No panel in a closet, none in a bathroom, and none over the steps of a stairway: three prohibitions together — the bathroom prohibition being the one that exempts supplementary overcurrent protection.
Exact wording
Overcurrent protective devices may not be located near easily ignitible material, such as in clothes closets, and may not be located in bathrooms, showering facilities, or locker rooms with showers, other than supplementary overcurrent protection. They may not be located over the steps of a stairway.
Electrical Code § 240.24
Mount the handles of breakers and fused switches no higher than 6 feet 7 inches.
Measure from the floor or working platform to the center of the handle, with the handle in its highest position. The devices must also be . Exceptions: supplementary overcurrent protection; busway devices and the service and outside-feeder disconnects their own articles cover; a device adjacent to the utilization equipment it supplies, which may be reached by portable means such as a ladder; and listed industrial control panels, hazardous-location enclosures, or environmental enclosures, which a tool may open — though the devices inside must still be readily accessible and within 6 feet 7 inches once the enclosure is open.
On the job
6 feet 7 inches to the center of the grip is the tested number. The exceptions are the qualifiers: supplementary devices, busway and service disconnects, portable-means access beside the equipment served, and the tool rule for sealed enclosures.
Exact wording
Breakers and fused switches must be readily accessible, with the handle's center no more than 6 feet 7 inches above the floor or working platform in its highest position, with exceptions: supplementary overcurrent protection is exempt; so are busway devices and the service and outside-feeder disconnects their own articles cover; a device adjacent to the utilization equipment it supplies may be reached by portable means such as a ladder; and a tool may be used to open listed industrial control panels, hazardous-location enclosures, or environmental enclosures, though the devices inside must still meet the accessibility and 6-foot-7 rules once the enclosure is open.
Electrical Code § 240.24
Keep every bored hole at least 1-1/4 inches back from the edge of the joist.
Measure at least 1-1/4 inches from the edge of the hole to the edge of the joist, rafter, or other wood member where a cable or raceway passes through. Where that distance cannot be held, protect the cable or raceway from nails and screws with a steel plate or bushing at least 1/16 inch thick covering the wiring. RMC, IMC, rigid PVC, RTRC, and EMT need no plate. A listed and marked thinner plate that protects as well is also allowed.
On the job
1-1/4 inches or a nail plate: the exam tests both the distance and the fix. Two outs: the tough conduit types (RMC, IMC, PVC, RTRC, EMT) need no plate at all, and a listed, marked thinner plate counts if it protects as well.
Exact wording
Where a cable or raceway runs through bored holes in joists, rafters, or other wood members, the edge of the hole stays at least 1-1/4 inches from the edge of the member. Where that distance cannot be kept, the cable or raceway is protected from nails and screws by a steel plate or bushing at least 1/16 inch thick covering the wiring, except that rigid metal conduit, intermediate metal conduit, rigid PVC, RTRC, and EMT need no plate, and a listed and marked thinner plate giving equal or better protection is allowed.
Electrical Code § 300.4
Take away
Important numbers to know
Where people go wrong
Sounds right: "Neutral and ground get bonded at every panel."
Where’s the catch?
Sounds right: "One ground rod is enough."
Where’s the catch?
Sounds right: "A water pipe electrode can stand alone if it measures well."
Where’s the catch?
Sounds right: "GFCI and AFCI do the same job."
Where’s the catch?
Sounds right: "A panel is fine in a closet if it stays accessible."
Where’s the catch?
Sounds right: "The working space is 3 feet only when nothing faces the panel."
Where’s the catch?
Sounds right: "The working space in front of a panel is 24 inches wide."
Where’s the catch?
Where to look it up
- Definitions (feeder, branch circuit, GEC, bonding jumpers, service lateral)
- CEC Article 100
- Working space, terminal torque
- CEC Article 110: 110.26 and Table 110.26(A)(1); 110.14(D)
- Required circuits, receptacle placement, GFCI, AFCI, multiwire circuits
- CEC Article 210: 210.11(C), 210.52, 210.8, 210.12, 210.4
- Overcurrent device locations
- CEC 240.24
- Grounding electrodes, separate buildings, EGC continuity
- CEC Article 250: 250.53, 250.32, 250.148
- Cable protection through framing
- CEC 300.4
- Receptacle replacement rules
- CEC 406.4(D)
Glossary
Every term this guide defines, in one place. Each is also defined where it first appears.
- Condition 1, 2, 3 (Table 110.26(A)(1))
- What faces the exposed live parts across the working space: Condition 1, no live or grounded parts opposite (or live parts guarded by insulation); Condition 2, grounded parts opposite, concrete, brick, and tile walls counting as grounded; Condition 3, exposed live parts on both sides.
- Grounded conductor
- A system or circuit conductor intentionally grounded. In the typical dwelling system, this is the neutral.
- Grounding electrode conductor (GEC)
- The conductor connecting the grounded conductor or equipment to the grounding electrode.
- Individual branch circuit
- A branch circuit that supplies only one utilization equipment.
- Main bonding jumper
- The connection at the service between the neutral and the equipment grounding conductor or supply-side bonding jumper.
- Multiwire branch circuit
- Two or more hot conductors sharing one neutral that has equal voltage to each.
- Readily accessible
- Reachable quickly for operation or inspection without tools (other than keys), climbing, removing obstacles, or ladders. Two relaxations for overcurrent devices: portable-means access where the device sits beside the equipment it supplies, and a tool to open certain listed or hazardous-location enclosures.
- Separately derived system
- A power supply output other than a service, with no direct connection to another source except through grounding and bonding: a transformer secondary or a generator with a switched neutral.
- Service point
- Where the utility's facilities connect to the premises wiring; the lateral (underground) or drop (overhead) ends here.
- Supplementary overcurrent protection
- Limited protection added in addition to the required branch-circuit overcurrent device; a device serving as the branch-circuit protection is not supplementary.
- Supply-side bonding jumper
- A conductor on the supply side of a service, within the service equipment, or for a separately derived system, that ensures the required electrical conductivity between metal parts required to be electrically connected.
- System bonding jumper
- The neutral-to-ground connection at a separately derived system; the main bonding jumper's counterpart.
- Ungrounded
- Not connected to ground or to a conductive body that extends the ground connection; an ungrounded conductor is the 'hot' conductor.
Keep going
- Practice questions for General Building (B) — Core Trades is 30% of the exam.
- Job scenario: Six Circuits and a Closet
- Job scenario: The Closet Heater
- Also in Core Trades: Core Trades: Seven Trades, One Section
- Also in Core Trades: HVAC: The Rules the Exam Asks For
- Also in Core Trades: Plumbing: The Rules the Exam Asks For
- Also in Core Trades: Building Envelope: The Rules the Exam Asks For
- Every number on one page — this guide’s figures alongside every other General Building (B) guide’s.
Test yourself: 10 questions for this guide
A paid account adds more ways to practice and prepare: study questions after every chapter, practice questions for every topic, timed practice exams, and job scenarios drawn from real jobs. A free account gets you one timed practice exam and saves your progress across devices. Here is one of this guide's questions:
Conductors run from the main panel to a subpanel in the garage. Feeder or branch circuit?
AnswerFeeder: they run between the service equipment and the final branch-circuit overcurrent device. Everything after that device is branch circuit.
Electrical Code § art100
Finished reading?
When you miss a question on this topic, we'll suggest a job scenario where there is one, rather than text you've already read. Finishing every chapter counts too.